CCA Conductivity, Resistance and Temperature Rise

Use conductivity to calculate resistance for a defined conductor. Establish current capability in the finished assembly with its insulation, installation, cooling and connections.

On this page

Separate the three questions

Conductivity describes a material at a stated temperature. Resistance adds the conductor’s length and metallic cross-section. Temperature rise depends on the complete heat-generating and heat-dissipating assembly. These quantities answer different design questions.

Scroll horizontally to view all columns.

← Scroll horizontally to see all columns →

QuestionInputsUseful output
What is the conductor resistance?Resistivity, temperature, length and metallic areaResistance over the stated length
What CCA section matches a copper resistance?Both resistivities at the same temperature and the copper sectionCandidate CCA metallic area
What current can the assembly carry?Conductor, insulation, terminals, enclosure, ambient and dutyAssembly test results against the applicable limits

Calculate on a consistent unit basis

Resistance is R = ρL/A. With resistivity in Ω·mm²/m, length in m and area in mm², the result is in Ω. For a round wire A = πd²/4; for a rectangular section A = width × thickness only where that describes the actual metallic section. Account for rounded corners and layers using the drawing or verified section data.

For equal length, temperature and resistance, A_CCA/A_Cu = ρ_CCA/ρ_Cu. This determines a candidate area, not a finished-cable current rating. Keep copper proportion by mass, volume or area explicit when choosing the material data.

Cross-section comparison of copper and CCA wire at equal diameter and equal resistance.
Cross-section comparison of copper and CCA wire at equal diameter and equal resistance. View full-size illustration

Check the dimensional consequences

For round wire, the area ratio changes diameter through its square root. For flat wire, allocate the candidate area within the available width and thickness, then check corner shape, bend direction and the insulated envelope. Terminal entry, tooling and joining surfaces must accommodate the actual construction.

Use the existing CCA comparison tools with the stated comparison basis. Keep density and purchased mass separate from the resistance calculation; neither proves assembly temperature rise.

Measure the assembly that will be used

Locate sensors on conductor sections, terminals, joints and the surrounding ambient. Test the actual current duty and installation, record the stabilization criterion, and compare temperature rise and absolute temperature with the design requirements. A local terminal hotspot may be missed by measuring only the conductor midspan.

Follow the temperature-rise measurement guide for a traceable setup. Provide the wire drawing, resistance target, installation and current duty for a CCA specification review.